Transformer; JSP Heat Pump Plant

Hange

Negotiated procedure without prior call for competition
15.05.2024 13:40 (GMT+03:00)

Hankija

Alva-yhtiöt Oy Alva-yhtiöt Oy
PL 4
40101 Jyväskylä
Finland
1071200-1

Eesmärk

The procurement is established to purchase 110/10,5 kV / 31,5 MVA (oil) transformer. Specific specification requirements: Construction •The transformer shall be delivered complete with all normal parts and accessories required for proper performance and transport. •The thermometers and oil level indicator shall be placed so that these can be read from the ground levels. •Each alarm and trip contact of the protective equipment shall be electrically separated from any other signals. Transformer type • Air-cooled oil transformer 3 phase. •Cooling method, ONAN. •Load will be at nominal load many hours per day. Nominal values •Nominal power (in all adjustment positions) 31,5 MVA ONAN. •Nominal voltage 117 ± 9 x 1.67/ 10,5 kV. •Frequency 50Hz. •Short circuit impedance 11% (±IEC tol.). •Switching group YNd11. •Standards: IEC 60076, IEC60354, and Genelec / SFS6001 •HV insulation level UM123, LI550, AC230. •MV insulation level UM24, LI170, AC28. Ambient conditions •Ambient air temperature range -40..+40°C. •The altitude above the sea level is well<1000 m. •The design ambient temperature at which the permissible temperature rises over ambient temperatures are defined is 20ºC. Requirements •The transformer tank and other parts in contact with the outside air must be reliably protected against corrosion. •dBA level requirement (normal PM 60-65 dBA). •Radiators shall be hot-dip galvanised (SFS-EN ISO 1461). •Oil-immersed, Radiator Tank Design with Conservator Tank. •The oil supplied shall be in accordance with IEC 60296 class II. •The necessary de-conservation and oil treatment at site after the transport are included in the scope of supply of the transformer. •The transformer tank shall be vacuum resistant. •The transformer tank shall also be painted on the inside with a suitable paint. •Corrosion protection class minimum C3. •Winding CU. •Heat stabilized insulating paper shall be used as insulation for the windings. •Munksjö Thermo 90 transformer paper. •Tier 2 classification. Inspection and testing •Auxiliary voltages available 220 VDC and 400/230AC. Voltages according IEC standard for below. •Insulation test voltage 50 Hz 1 min, voltage specified on each transformer below. •Control and signalling circuits test. •Surge voltage withstand. •Overvoltage test. Load capacity •Load capacity according to IEC. Highest accepted temperatures at nominal load: •Winding temperature rise at warmest point 65K. •Oil temperature rise 60K. •At highest control point it is allowed 5K higher temperatures. Protection devices •Gas relay with separate alarm and trigger contacts. •Gas relay test pump. •Transformer tank relief valve(s) with trigger contact(s). •Oil thermometer with alarm and trip contacts. •Oil level indicator with alarm contact (for expansion tanks). •The Pt 100 sensor is for remote measurement of oil temperature, mA converter 4...20 mA should be included. •Winding temperature display with the necessary current transformers and with alarm and trip contacts. •The Pt 100 sensor is for remote measurement of the winding temperature and the transformer temperature, all winding temperature measurements shall be duplicated, mA converter 4...20 mA should be included. •Motor protection relay for the on-load tap changer. •Oil level indicator for on load tap changer. •Separate dehumidifiers for transformer and on load tap changer. Other •Delivery to the site (JSP Heat pump plant, Raivionsuntti 10, 40520 Jyväskylä, Finland), including successful installation, testing and commissioning to be completed by 31.08.2025, and documentation provided thereof in English or Finnish. •In line with section 97 of UtilAct, a tender submitted for the award of a supply contract may be rejected where the proportion of the products originating in third countries, as determined in accordance with Regulation (EU) No 952/2013 of the European Parliament and of the Council, exceeds 50 % of the total value of the products constituting the tender. This applies to products originating in third countries with which the EU has not concluded, whether multilaterally or bilaterally, an agreement ensuring comparable and effective access for Union undertakings to the markets of those third countries.

Mercell Estonia OÜ

Mercelli gruppi kuuluv Euroopa juhtiv e-hanke keskkond vahendab infot ostjate ja tarnijate vahel.

Kontakt

Mercell Eesti kasutajatugi

+372 683 6785
Mercell Estonia OÜ | Põhja puiestee 21C, 10143 Tallinn, Eesti