Development Project for a Seventh Heat Pump Unit for Helen Ltd Katri Vala Heat Pump Station

Hange

06 - Contract award notice - utilities
Läbirääkimistega menetlus
29.07.2020 10:31 (GMT+03:00)

Hankija

Helen Ltd Helen Ltd
Sari Aapro
Kampinkuja 2
00100 Helsinki
Finland
2630573-4

Eesmärk

A development project to design and build up one heat pump. The designed heat pump unit has to meet following requirements: — refrigerant R1234ze; — as high heating capacity as possible; — maximum dimensions of the unit 20 m x 10 m x 8 m (length x width x height) approximately; — maximum heating outlet temperature ≥ 95 ºC; — sewage water to evaporator. Approved compressor type: turbo compressor. The heat pump unit shall be designed so that: (a) inlet temperature of sewage water to evaporator varies between + 6-20 ºC; (b) inlet temperature of district heating water to condenser varies between + 37-60 ºC.